Filter
Outdoor Sensors
AGS55+
Outdoor temperature sensor with external stainless steel probe (fast response) for measuring temperature in outdoor areas, cold rooms, greenhouses, production plants and warehouses. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation.
Application/type | Outdoor sensor |
---|---|
Purpose | Measure values |
Measured values | temperature |
Interface | LoRaWAN® (868 MHz), RS485 Modbus, RS485 BACnet, LON FT, Passive, Active, 0..5 V, 0..10 V, 4..20 mA, Switch contact |
Configuration | USEapp, uConfig, BUS, jumper, DIP switches, LoRaWAN® Downlink, (depending on type) |
Sensor | SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), PT1000 DIN cl. B, PT100 DIN cl. B, PT1000 1/3 DIN, PT100 1/3 DIN, Ni1000 DIN cl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC10K Carel, NTC20K, NTC1,8K, NTC5K, LM235Z, KTY81-110, KTY81-121, KTY81-122, KTY81-210, DS18B20 1-wire, FeT/Staefa, passive |
Output voltage | 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 5 kΩ, min. load 10 kΩ |
Output current | 4..20 mA, max. load 500 Ω |
Output switch contact | 2x floating contact NO for 24 V ~ or 24 V = / 3 A |
Network technology | RS485 Modbus, RS485 BACnet (MS/TP), LON FT (free topology) |
Radio technology | LoRaWAN® (868 MHz) |
Data transmission | bidirectional, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | -35..+90 |
Operating ranges temperature (°C) | -35..+70, -20..+70, -35..+90 |
Output signal temperature | scaling analogue output, -20..+80 °C (default setting), -50..+50 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer, optionally configurable |
Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range, ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C, temperature dependend), potentiometer for offset adjustment, offset setting via app or uConfig |
Power supply | 15..24 V = (±10%) SELV, 15..35 V = SELV, 24 V ~ (±10%) SELV, 19..29 V ~ SELV |
Power consumption | typ. 0,4 W (24 V =), typ. 0,5 W (24 V =), max. 0,7 W (24 V =), max. 2,5 W (24 V =), 0,8 VA (24 V ~), 1,8 VA (24 V ~), 4,3 VA (24 V ~) |
Material in touch with media | Sensor probe, Ø=6 mm, stainless steel V2A (1.4305), length 25 mm, for faster response |
Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | USE-S, impact- and shock-resistant enclosure with quick-release cover, PC, USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white, transparent cover |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm², relay max. 1,5 mm² |
Connection cable | 2-wire, 3-wire, 4-wire |
Delivery content | incl. mounting base enclosure USE-S pure white, incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
Packaging | case packaging |
Notes | external antenna available on request |
Option enclosure | LCD 29x35 mm, RGB backlight |
Vorschau | Name |
---|---|
AGS55-Plus_Header.jpg |
No tender texts available