Application/type |
Duct sensor, Immersion sensor |
Purpose |
Measure values |
Measured values |
temperature |
Interface |
RS485 Modbus |
Configuration |
BUS, DIP switches |
Sensor |
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Network technology |
RS485 Modbus |
Data transmission |
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) |
-50..+160 |
Operating ranges temperature (°C) |
-50..+160 |
Operating range temperature enclosure (°C) |
-35..+70 |
Operating range humidity |
max. 85% rH short term condensation |
Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range |
Power supply |
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption |
max. 0,7 W (24 V =), 1,8 VA (24 V ~) |
Material in touch with media |
Sensor probe, Ø=6 mm, stainless steel V4A (1.4571), suitable for usage in aggressive media |
Installation length (mm) |
50, 100, 150, 200, 250, 300, 450 |
Enclosure |
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour |
pure white, transparent cover |
Protection (IP) |
IP65, according to EN 60529 |
Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Mounting |
when used as duct sensors: please use mounting flange MF6DS flexible (+90..+120 °C) or MF6 (brass, +120..+260 °C), or with enclosure USE-S with mounting clip, for use as immersion sensors please use immersion pocket THVADS / THMSDS |
Delivery content |
incl. mounting clip enclosure USE-S pure white, incl. mounting set (screws and accessories) |
Packaging |
case packaging |
Option enclosure |
LCD 29x35 mm, RGB backlight |