DLF
DLF1 V G1/4"
Pressure transducer fluids, air or other non-flammable/non-aggressive gases
pressure 0..1 bar | Active, 0..10 V | IP65 according to EN 60529
Application/type | Pressure transducer |
---|---|
Purpose | Measure values |
Measured values | pressure |
Interface | Active, 0..10 V |
Output voltage | 0..10 V, min. load 5 kΩ |
Operating range temperature (°C) | -40..+125 |
Operating ranges temperature (°C) | -40..+125 |
Operating range temperature enclosure (°C) | -40..+105 |
Operating range pressure | fluids, air or other non-flammable/non-aggressive gases |
Measuring range pressure | 0..1 bar |
Accuracy pressure | ±0,5% (typ. at 21 °C) |
Power supply | 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption | typ. 0,15 W (24 V =), 0,3 VA (24 V ~) |
Material in touch with media | stainless steel V2A (1.4305), G1/4" |
Protection (IP) | IP65, according to EN 60529 |
Connection | cable gland for wires with Ø=8 mm max., plug MVS according to DIN 175301-803 |
Packaging length (mm) | 170 |
Packaging width (mm) | 120 |
Device length (mm) | 50 |
Device width (mm) | 35 |
Device height (mm) | 97 |
Weight (g) | 60 |
Catalogue table | Pressure transducer |